PROMASEAL® Collar

ADVANTAGES

  • Supplied pre-assembled, and available in variety of sizes 
  • Ease of fixing to suit location – 5 fixing types tested (fixings not supplied) 
  • Can be fixed directly to PROMASEAL® Fire Barrier batts. 
  • Up to 240 minutes fire resistance 
  • UL-EU Approval 
  • Allows thermal and mechanical movement of the pipe. 
  • Can be used with plastic and insulated metal pipes. 
  • Halogen free, contains no asbestos, ceramic or mineral fibres 

PROMASEAL® COLLAR comprises of an intumescent component incorporated into a mild steel case and is designed and tested to seal plastic and insulated metal pipes.

Tested to EN 1366-3 to provide up to EI 120 (Drywall, concrete and masonry walls) and EI 240 (concrete floors).
Available in a range of sizes, maximum diameter 250mm. Colour: Blue

More Information

i  Request Samples

Applications

Performance
< #Back#
PROMASEAL® COLLAR includes an intumescent component incorporated into a mild steel case to close any gaps and to provide a closure of combustible pipes when heated, to prevent the passage of fire.
PROMASEAL® COLLAR includes an intumescent component incorporated into a mild steel case to close any gaps and to provide a closure of combustible pipes when heated, to prevent the passage of fire.
Installation
< #Back#
  • Ensure that the aperture and services in question have been tested with PROMASEAL® COLLAR and the site conditions are within the application specification. Services to be rigidly supported maximum 400mm from the seal on both sides of the wall and floor. 
  • All services and apertures need to be clean and clear of all dust and loose particles. The aperture temperature needs to be at +5 deg C or above at time of installation.
  • An annular space (max 10mm annular) needs to be present around the service to apply sufficient installation depth of PROMASEAL® Intumescent Acrylic Sealant.
  • Upon installation make sure that the annular gap around the pipe is filled with the PROMASEAL® Intumescent Acrylic Sealant.
  • Install the PROMASEAL® COLLAR around the pipe and fix the collar to the wall or floor with the recommended fixings.
  • Ensure that the aperture and services in question have been tested with PROMASEAL® COLLAR and the site conditions are within the application specification. Services to be rigidly supported maximum 400mm from the seal on both sides of the wall and floor. 
  • All services and apertures need to be clean and clear of all dust and loose particles. The aperture temperature needs to be at +5 deg C or above at time of installation.
  • An annular space (max 10mm annular) needs to be present around the service to apply sufficient installation depth of PROMASEAL® Intumescent Acrylic Sealant.
  • Upon installation make sure that the annular gap around the pipe is filled with the PROMASEAL® Intumescent Acrylic Sealant.
  • Install the PROMASEAL® COLLAR around the pipe and fix the collar to the wall or floor with the recommended fixings.
Documents
< #Back#

Product Data Sheets